Events and registers
The fault locator function (abbreviated "EMON" in event block names) generates events and registers
from the status changes in triggering calculation. The user can select the status ON or OFF for
messages in the main event buffer.
The triggering event of the function is recorded with a time stamp and with process data values.
Table. 5.3.8. - 75. Event codes.
Event number
Event channel
Event block name
Event code
Description
8658
135
EMON1
18
FL (21FL) Triggered ON
8659
135
EMON1
19
FL (21FL) Triggered OFF
The table below presents the structure of the function's register content. This information is available
for the last twelve (12) recorded events.
Table. 5.3.8. - 76. Register content.
Date and
time
Event
code
Fault type
Fault direction
Fault
reactance
Fault
distance
Used SG
dd.mm.yyyy
hh:mm:ss.mss
6336-
6383
Descr.
L1-L2; L2-L3; L3-L1; L1-N;
L2-N; L3-N; L1-L2-L3
Not detected;
Forward; Reverse
In ohms
In
kilometers
Setting
group 1...8
active.
5.4. General menu
The
General
menu consists of basic settings and indications of the device. Additionally, the all
activated functions and their status are displayed in the
Protection
,
Control
and
Monitor
pro les.
Table. 5.4. - 77. Parameters and indications in the
General
menu.
Name
Description
Range
Step
Default
Device name
The le name uses these elds when loading the aqs con guration
le from the AQ-200 unit.
-
-
Unitname
Device location
-
-
Unitlocation
Timesync. source
If an external clock time synchronization source is available, the type
is de ned with this parameter. In the internal mode there is no
external Timesync source. IRIG-B requires a serial ber
communication option card.
0: Internal
1: External
NTP
2: External
Serial
3: IRIG-B
-
0: Internal
Enable stage
forcing
When this parameter is enabled it is possible for the user to force the
protection, control and monitoring functions to different statuses like
START and TRIP. This is done in the function’s
Info
page with the
Status force to
parameter.
0: Disabled
1: Enabled
-
0: Disabled
System phase
rotating order
Allows the user to switch the expected order in which the phase
measurements are wired to the unit.
0: A-B-C
1: A-C-B
-
0: A-B-C
Language
Changes the parameter description languages in the HMI.
0: User
de ned
1: English
2: Suomi
3: Svenska
4: Español
5: Français
-
1: English
Clear events
Clears the event history recorded in the AQ-200 device.
0: -
1: Clear
-
0: -
LCD Contrast
Changes the contrast of the LCD display.
0…255
1
120
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
92
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...