There are several different ways to use all four voltage channels. The voltage measurement modes are
the following:
3LN+U0 (three line-to-neutral voltages and the measured zero sequence voltage U0)
3LN+U4 (three line-to-neutral voltages and the U4)
3LL+U4 (three line-to-line voltages and the U4)
2LL+U3+U4 (two line-to-line voltages, the U3, and the U4)
The 3LN+U0 is the most common voltage measurement mode. See below for example connections of
voltage line-to-line measurement (3LL on the left, 2LL on the right).
Figure. 5.2.2. - 43. Example connections for voltage line-to-line measurement.
If only two line-to-line voltages are measured, the third one (U
L31
) is calculated based on the U
L12
and
U
L23
vectors. When measuring line-to-line voltages, the line-to-neutral voltages can also be calculated
as long as the value of U0 is measured and known.
The voltage measurement channel U4 can also be used to measure either the zero sequence voltage
(U0) or the side 2 voltage (Synchrocheck). If the 2LL+U3+U4 mode is selected, the third channel (U3)
can be used for this purpose. Please note that U0 can only be measured by using a single channel.
In the image below is an example of 2LL+U0+SS, that is, two line-to-line measurements with the zero
sequence voltage and voltage from side 2 for Synchrocheck. Since U0 is available, line-to-neutral
voltages can be calculated.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
50
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...