MBIO ModB
Ch x Invalid
Channel 1...8 of MBIO Mod C is
invalid
Ph.Rotating Logic control
0=A-B-C, 1=A-C-B
Phase rotating order at the moment. If
true ("1") the phase order is reversed.
NOTE! Digital channels are measured every 5 ms.
Recording settings and triggering
Disturbance recorder can be triggered manually or automatically by using the dedicated triggers. Every
signal listed in "Digital recording channels" can be selected to trigger the recorder.
The device has a maximum limit of 100 for the number of recordings. Even when the recordings are
very small, their number cannot exceed 100. The number of analog and digital channels together with
the sample rate and the time setting affect the recording size. See calculation examples below in the
section titled "Estimating the maximum length of total recording time".
Table. 5.6.1. - 103. Recorder control settings.
Name
Range
Step
Default
Description
Recorder
enabled
0: Enabled
1: Disabled
-
0:
Enabled
Enables and disables the disturbance recorder function.
Recorder
status
0: Recorder
ready
1: Recording
triggered
2: Recording and
storing
3: Storing
recording
4: Recorder full
5: Wrong con g
-
0:
Recorder
ready
Indicates the status of recorder.
Clear
0…2
32
-1
1
-
Clears selected recording. If "1" is inserted, rst recording will be
cleared from memory. If "10" is inserted, tenth (10th) recording will be
cleared from memory.
Manual
trigger
0: -
1: Trig
-
0: -
Triggers disturbance recording manually. This parameter will return
back to "-" automatically.
Clear all
records
0: -
1: Clear
-
0: -
Clears all disturbance recordings.
Clear newest
record
0: -
1: Clear
-
0: -
Clears the newest stored disturbance recording.
Clear oldest
record
0: -
1: Clear
-
0: -
Clears the oldest stored disturbance recording.
Max. number
of recordings
0…100
1
-
Displays the maximum number of recordings that can be stored in
the device's memory with settings currently in use. The maximum
number of recordings can go up to 100.
Max. length
of a
recording
0.000...1800.000
s
0.001
s
-
Displays the maximum length of a single recording.
Max. location
of the pre-
trigger
0.000...1800.000
s
0.001
s
-
Displays the highest pre-triggering time that can be set with the
settings currently in use.
Recordings
in memory
0…100
1
-
Displays how many recordings are stored in the memory.
Table. 5.6.1. - 104. Recorder trigger setting.
Name
Description
Recorder
trigger
Selects the trigger input(s). Clicking the "Edit" button brings up a pop-up window, and checking the boxes
enable the selected triggers.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
124
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...