Control
termination
timeout
0.02…
500.00
s
0.02
s
10 s
Determines the control pulse termination timeout. If the object has not changed it
status in this given time the function will issue error event and the control is ended.
This parameter is common for both open and close commands.
Final trip
pulse
length
0.00…
500.00
s
0.02
s
0.2 s
Determines the length of the nal trip pulse length. When the object has executed
the nal trip, this signal activates. If set to 0 s, the signal is continuous. This can be
used in the matrix or in Logic editor.
Table. 5.5.2. - 86. Control settings (DI and Application).
Signal
Range
Description
Access level for MIMIC
control
0: User
1: Operator
2: Con gurator
3: Super user
De nes what level of access is required for MIMIC control. The
default is the "Con gurator" level.
Objectx LOCAL
Close control input
Digital input or other logical signal
selected by the user
The local Close command from a physical digital input (e.g. a
push button).
Objectx LOCAL
Open control input
Digital input or other logical signal
selected by the user
The local Open command from a physical digital input (e.g. a
push button).
Objectx
REMOTE Close control
input
Digital input or other logical signal
selected by the user
The remote Close command from a physical digital input (e.g.
RTU).
Objectx REMOTE
Open control input
Digital input or other logical signal
selected by the user
The remote Open command from a physical digital input (e.g.
RTU).
Objectx Application
Close
Digital input or other logical signal
selected by the user
The Close command from the application. Can be any logical
signal.
Objectx Application
Open
Digital input or other logical signal
selected by the user
The Close command from the application. Can be any logical
signal.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Blocking and interlocking
The interlocking and blocking conditions can be set for each controllable object, with Open and Close
set separately. Blocking and interlocking can be based on any of the following: other object statuses, a
software function or a digital input.
The image below presents an example of an interlock application, where the closed earthing switch
interlocks the circuit breaker close.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
104
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...