The application-controlled setting group change can also be applied entirely from the relay's internal
logics. For example, the setting group change can be based on the cold load pick-up function (see the
image below).
Figure. 5.5.1. - 67. Entirely application-controlled setting group change with the cold load pick-up function.
In this example the cold load pick-up function's output is used for the automatic setting group change.
Similarly to this application, any combination of the signals available in the relay's database can be
programmed to be used in the setting group selection logic.
As all these examples show, setting group selection with application control has to be built fully before
they can be used for setting group control. The setting group does not change back to SG1 unless it is
controlled back to SG1 by this application; this explains the inverted signal NOT as well as the use of
logics in setting group control. One could also have SG2 be the primary SG, while the ON signal would
be controlled by the higher priority SG1; this way the setting group would automatically return to SG2
after the automatic control is over.
Events
The setting group selection function block (abbreviated "SGS" in event block names) generates events
from its controlling status, its applied input signals, enabling and disabling of setting groups, as well as
unsuccessful control changes. The function does not have a register.
Table. 5.5.1. - 81. Event codes.
Event number
Event channel
Event block name
Event code
Description
4160
65
SGS
0
SG2 Enabled
4161
65
SGS
1
SG2 Disabled
4162
65
SGS
2
SG3 Enabled
4163
65
SGS
3
SG3 Disabled
4164
65
SGS
4
SG4 Enabled
4165
65
SGS
5
SG4 Disabled
4166
65
SGS
6
SG5 Enabled
4167
65
SGS
7
SG5 Disabled
4168
65
SGS
8
SG6 Enabled
4169
65
SGS
9
SG6 Disabled
4170
65
SGS
10
SG7 Enabled
4171
65
SGS
11
SG7 Disabled
4172
65
SGS
12
SG8 Enabled
4173
65
SGS
13
SG8 Disabled
4174
65
SGS
14
SG1 Request ON
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
98
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...