9.1.1.4. Frequency measurement
Table. 9.1.1.4. - 141. Frequency measurement accuracy.
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to the 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2. CPU & Power supply
9.1.2.1. Auxiliary voltage
Table. 9.1.2.1. - 142. Power supply model A
Rated values
Rated auxiliary voltage
85…265 V (AC/DC)
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 60 ms with 110 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Table. 9.1.2.1. - 143. Power supply model B
Rated values
Rated auxiliary voltage
18…72 VDC
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 90 ms with 24 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.2.2. CPU communication ports
Table. 9.1.2.2. - 144. Front panel local communication port.
Port
Port media
Copper Ethernet RJ-45
Number of ports
1
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
190
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...