9PX PowerPass

®

 Distribution Modules and Transformers

9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1
User's Guide

®

For use with 9PX 5000/6000/8000/11000 VA UPS Models

Содержание PowerPass 9PXTFMR5

Страница 1: ...Eaton 9PX PowerPass Distribution Modules and Transformers 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide For use with 9PX 5000 6000 8000 11000 VA UPS Models ...

Страница 2: ... the user will be required to correct the interference at his own expense EN 62040 2 Some configurations are classified under EN 62040 2 as Class A UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a domestic environment this product may cause radio interference in which case the user may be required to take additional m...

Страница 3: ...Directives 2006 95 EC Council Directive on equipment designed for use within certain voltage limits 2004 108 EC Council Directive relating to electromagnetic compatibility The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Power Quality SAS 110 Rue Blaise Pascal 38334 St ISMIER FRANCE Phone 33 476 00 6...

Страница 4: ...ional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or...

Страница 5: ... Checking the Accessories 7 Tower Setup 9 Rackmount Setup 10 Installing the Rails 11 Installing the Cabinet 12 4 Electrical Installation 15 9PXPPDM2 Electrical Installation 16 Requirements 16 Procedure 17 9PXTFMR11 Electrical Installation 20 Requirements 20 Procedure 21 9PXPPDM1 and 9PXTFMR5 Electrical Installation 23 Requirements 23 Procedure 25 5 Voltage Selection 27 9PXPPDM1 and 9PXPPDM2 Voltag...

Страница 6: ...age Selection 32 Settings 32 Procedure 33 6 Startup 35 Startup with the UPS 35 Plug Receptacle Connections 37 System Configuration Connections 40 7 Maintenance Bypass 45 Using Maintenance Bypass 45 Return to Normal UPS Protection 46 8 Specifications 49 Specification Tables 49 Rear Panels 52 9 Service and Support 55 ...

Страница 7: ...rovide surge protection if the UPS is not present S Provide extra surge protection when the UPS is present S Replace or upgrade the UPS without losing power to the protected equipment using the Maintenance Bypass feature for 9PX PPDMs only S Voltage selection for 208 Vac or 240 Vac input S Choice of plug receptacle or terminal block wired models S Variety of output outlets S Breaker protection S B...

Страница 8: ...nt Cover with Center Cover Attached all models Front Cover with Center Cover Removed to Access Bypass Switch 9PX PPDMs only Front Cover with Center Cover Open to Access Voltage Selection Switch all models except 9PXTFMR11 which uses terminal block wiring for voltage selection 208V 2 4 0 V UPS B Y P A S S 208V 2 4 0 V NORMAL BYPASS Figure 1 Front Cover and Operation Switches ...

Страница 9: ...onfigured with a 5000 VA 9PX UPS S 9PXPPDM1 configured with a 6000 VA 9PX UPS S 9PXPPDM2 configured with a 5000 VA 9PX UPS S 9PXPPDM2 configured with a 6000 VA 9PX UPS 9PX Transformer Models The 9PX Transformer models are combined with 9PX 5000 6000 8000 11000 VA UPS models as well as EBMs and MBPs in five system configurations S 9PXTFMR5 with a 5000 VA 9PX UPS S 9PXTFMR5 with a 6000 VA 9PX UPS S ...

Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4 ...

Страница 11: ...ndoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum S For models with terminal block wired outputs 9PXPPDM2 and 9PXTFMR11 overcurrent protection for the output AC circuit s is to be provided by others S For pluggable equipment 9PXPPDM1 and 9PXTFMR5 the socket outlet shall be installed near the e...

Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6 ...

Страница 13: ...pping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative Checking the ...

Страница 14: ... Mounting brackets and mounting screws for rackmount cabinet installation in the accessory box 9PXTFMR11 models only 1 Transformer cable used from UPS Output to Transformer Input in the accessory bag 9PXPPDM2 and 9PXTFMR11 models only 2 Cable glands used as strain relief for hardwired cables between the UPS and the 9PXPPDM2 or 9PXTFMR11 in the accessory bag Table 2 lists the tools that are needed ...

Страница 15: ... in the appropriate 9PX UPS user s guide for your system configuration NOTE Eaton recommends a minimum of 150 mm 5 9 free space behind the UPS rear panel 2 Position the cabinet upright Turn the Eaton logo to align with the top of the cabinet Ensure additional cabinets are upright 3 Group the cabinets in the correct order NOTE Joining brackets are required to stabilize the upright cabinets in insta...

Страница 16: ...e 2 Joining Brackets 9PXTFMR11 9PX 240V EBM and 9PX 11k UPS shown 6 Continue to Electrical Installation on page 15 Rackmount Setup NOTE The order of a rackmount installation from top to bottom is the 9PX UPS 9PX EBM and the 9PX PPDM or 9PX Transformer NOTE First install the rails in the rack Then install the cabinet on the rails ...

Страница 17: ...r below the UPS if the EBM is not installed in this configuration 3 Place the rails on the inside of the rack posts with the cabinet mounting flanges facing inside the rack The L Left or R Right letter on the side of the rail should also face inside the rack see Figure 3 4 Slide the rail to fit between the vertical rack posts 5 Secure each rail to the front and rear of the rack with two M6 12 mm s...

Страница 18: ...sformer Refer to shutdown instructions in the appropriate 9PX UPS user s guide for your system configuration 2 Place the cabinet on a flat stable surface with the front of the cabinet facing you 3 Align the mounting brackets with the screw holes on the side of the cabinet Install the mounting brackets see Figure 4 Rack mounting Bracket Figure 4 Installing Mounting Brackets 4 Set the rear of the ca...

Страница 19: ...k 5 Secure the front of the cabinet to the rack with two M6x12 mm round head screws Note the position of the screws in the installation front view see Figure 6 UPS EBM 9PX Transformer or 9PX PPDM Two M6x12 Rail mounting Screws Two M6x12 Cabinet mounting Bracket Screws Figure 6 Cabinet installed in Rack Front view 6 Continue to Electrical Installation on page 15 ...

Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14 ...

Страница 21: ...rrent protection for the output AC circuit s is to be provided by others S For 9PXPPDM1 and 9PXTFMR5 only For pluggable equipment the socket outlet shall be installed near the equipment and shall be easily accessible S Disconnection Device For 9PXPPDM2 a disconnect switch shall be provided by others for AC input and output circuit S Disconnection Device For 9PXTFMR11 the disconnection device of th...

Страница 22: ...wing requirements S 30A circuit with short circuit and overcurrent protection S 208 240 Vac S Single phase S 50 60 Hz S Breaker must be wall mounted and readily accessible to the operator S Flexible metal conduit recommended for ease of service and maintenance Figure 7 shows the 9PXPPDM2 block diagram The 9PXPPDM2 I O terminal block is hardwired Voltage Selection To UPS Output From UPS Input Trans...

Страница 23: ...ls on page 52 3 On the front cover unsnap and remove the square center cover 4 Verify that the bypass switch is in the UPS normal position S If the bypass switch is set to UPS replace the square center cover and go to Step 5 S If the bypass switch is set on Bypass turn the bypass switch to the UPS normal position see Figure 8 Replace the square center cover and go to Step 5 208V 2 4 0 V NORMAL BYP...

Страница 24: ...duit leaving approximately 0 5m 2 ft of exposed wire Attach a flexible metal fitting to the end of each conduit 8 On the UPS insert each conduit through a wiring access entry Strip 9 mm 0 35 of insulation from the end of each incoming wire 9 On the 9PXPPDM2 terminal block wire the UPS connections terminals 1 3 and attach the cable gland to the panel see Figure 10 and Table 4 10 To wire the load co...

Страница 25: ...l Block Table 4 9PXPPDM2 Wiring Specifications Terminal Position 9PXPPDM2 Wire Function Terminal Wire Size Rating Tightening Torque 1 Source Input Line 1 10 16 mm2 8 6 AWG 1 8 0 22 Nm 16 2 lb in 2 Source Input Line 2 3 Input Ground 6 16 mm2 10 6 AWG 4 Output Line 1 10 16 mm2 8 6 AWG 5 Output Neutral 6 Output Line 2 7 Output Ground 6 16 mm2 10 6 AWG Use 8 AWG for 9PXPPDM2 75_C copper wire minimum 1...

Страница 26: ... and overcurrent protection S 208 240 Vac S Single phase S 50 60 Hz S Breaker must be wall mounted and readily accessible to the operator S Flexible metal conduit recommended for ease of service and maintenance Figure 11 shows the 9PXTFMR11 block diagram The 9PXTFMR11 I O terminal block is hardwired The voltage selection terminal block must be wired with flexible wiring Voltage Selection L1 L2 G N...

Страница 27: ...n the cover and screw see Figure 12 OUTPU T OUTPU T NORMAL AC SOURCE NORMAL AC SOURCE 208V 240V SELEC T Remove Screw Punch Out Knock out Holes Normal AC Source Output Figure 12 Removing the Terminal Block Cover 4 Punch out the pre cut knock out holes for the input and output conduit 5 Pull the input and output wires through separate conduit leaving approximately 0 5m 2 ft of exposed wire Attach a ...

Страница 28: ... connections terminals 4 6 observe the following S Connect 4 and 6 line to line for 240V S Connect 5 and 6 line to neutral for 120V S Connect 4 and 5 line to neutral for 120V 10 Connect 7 output ground OUTPUT NORMAL AC SOURCE N L 2 N 1 2 3 4 5 6 7 120V 120V 240V L 1 L 1 L 2 Source Input Line 1 Source Input Line 2 Input Ground Output Line 1 Output Line 2 Output Ground Output Neutral UPS Connections...

Страница 29: ...6 AWG 6 Output Line 2 6 AWG 7 Output Ground 6 AWG Use 6 AWG for 9PXTFMR11 90_C copper wire minimum 11 Attach the cable gland to the panel 12 Replace the terminal block cover and secure with screw 13 Continue to Voltage Selection on page 27 to set the voltage selection 9PXPPDM1 and 9PXTFMR5 Electrical Installation This section provides terminal block wiring requirements and electrical installation ...

Страница 30: ...200 Rev 4 24 Figure 14 shows the 9PXPPDM1 block diagram To UPS Output Transformer AC Input Transformer AC Output From UPS Input Voltage Selection 30A MB L6 30R 5 20R x3 20A CB 30A L14 30R 5 20R x3 30A CB L6 30R L6 30P L6 30P L1 L2 N 120 120 240 L1 L2 G G G 20A CB Figure 14 9PXPPDM1 Block Diagram ...

Страница 31: ... AC Output L1 L2 N 120 120 5 20R x3 20A CB 20A CB 20A CB 20A CB L1 L2 G G 5 20R x3 5 20R x3 5 20R x3 L6 30P 30A 5 20R x3 5 20R x3 Figure 15 9PXTFMR5 Block Diagram Procedure For the 9PXPPDM1 and 9PXTFMR5 plug receptacle models 1 Verify that the output circuit breaker is in the OFF position see Rear Panels on page 52 2 9PXTFMR5 only Go to Step 5 3 9PXPPDM1 only On the front cover unsnap and remove t...

Страница 32: ...ypass switch is set to UPS replace the square center cover and go to Step 5 S If the bypass switch is set on Bypass instead turn the bypass switch to the UPS normal position see Figure 16 Replace the square center cover and go to Step 5 208V 2 4 0 V NORMAL BYPASS Figure 16 Resetting the Switch to UPS Normal 5 Continue to Voltage Selection on page 27 to set the voltage selection ...

Страница 33: ...e UPS output voltage The L14 30 and all low voltage receptacles use the transformer and the voltage switch determines the voltage NOTE The 9PXTFMR11 does not have a voltage switch The voltage must be wired in the voltage selection terminal block When the voltage selection is set to the 240V position with 240V input the output voltage is 240 120V When the voltage selection is set to 208V with 208V ...

Страница 34: ...O Voltage Settings Input Voltage from UPS 9PXPPDM1 Output Voltage 208V Switch Position Default 240V Switch Position L6 30R 5 20R L14 30R L6 30R 5 20R L14 30R 200 231 115 231 115 200 100 200 100 208 240 120 240 120 208 104 208 104 220 254 127 254 127 220 110 220 110 230 265 133 265 133 230 115 230 115 240 277 138 277 138 240 120 240 120 Table 7 9PXPPDM2 I O Voltage Settings Input Voltage from UPS 9...

Страница 35: ...o left side Phillips head screws that secure the front cover see Figure 17 Remove Screws 208V 2 4 0 V NORMAL BYPASS Figure 17 Remove the Front Cover Screws 3 Open the front cover from the left side see Figure 18 208V 2 4 0 V UPS B Y P A S S Figure 18 Open the Front Cover 4 Turn the switch to the selected voltage 5 Close the front cover and secure it with the two Phillips head screws 6 Replace the ...

Страница 36: ...PXTFMR5 I O Voltage Settings Input Voltage from UPS 9PXTFMR5 Output Voltage 208V Switch Position 240V Switch Position 5 20R 5 20R 200 115 100 208 120 104 220 127 110 230 133 115 240 138 120 250 144 125 Procedure To change the 9PXTFMR5 voltage switch position 1 On the 9PXTFMR5 front cover unsnap and remove the square center cover 2 Remove and retain the two left side Phillips head screws that secur...

Страница 37: ...front cover from the left side see Figure 20 208V 2 4 0 V UPS B Y P A S S Figure 20 Open the Front Cover 4 Turn the switch to the selected voltage 5 Close the front cover and secure it with the two Phillips head screws 6 Replace the square center cover 7 For startup with the UPS go to Chapter 4 Startup on page 35 ...

Страница 38: ...1 I O Voltage Settings for Voltage Selection Terminal Block Input Voltage from UPS 9PXTFMR11 Output Voltage 208V Setting 240V Setting HV LV HV LV 200 231 115 200 100 208 240 120 208 104 220 254 127 220 110 230 265 133 230 115 240 277 138 240 120 250 288 144 250 125 Table 10 9PXTFMR11 I O Voltage Settings for Plug Receptacles Input Voltage from UPS 9PXTFMR11 Output Voltage 208V Setting 240V Setting...

Страница 39: ... 240V SELEC T Normal AC Source Output Figure 21 Remove the Voltage Selection Terminal Block Cover 2 On the voltage selection terminal block use 6 AWG wire to connect a jumper from the middle terminal to either the 208V left or 240V right terminal see Figure 22 208V 240V SELECTION Connect Terminals 2 1 for 208V Connect Terminals 2 for 240V 1 2 3 3 208V 240V Figure 22 Wire Selected Voltage 3 Replace...

Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34 ...

Страница 41: ...ecommended upstream protection For European models also refer to the recommendations for downstream protection NOTE Before startup refer to the 9PX UPS EBM MBP user s guides for additional configuration information NOTE To change the UPS default settings refer to Display Functions in the UPS user s guide Refer to the UPS user s guide for UPS operation 1 Ensure that the upstream circuit breaker is ...

Страница 42: ... the UPS beep approximately three seconds After the UPS is turned on it conducts a self test and enters Normal mode The indicator remains on indicating that power is available to your equipment 7 Confirm the UPS output voltage through the front panel and verify that it matches the 9PX PPDM or 9PX Transformer output voltage For example if the input to the UPS is 208V then voltage selection should b...

Страница 43: ...d into the appropriate L1 or L2 receptacle group as illustrated in Figure 23 through Figure 28 CAUTION S Observe the appropriate load output limits when connecting for your model CIRCUI TBREAKER 120V 20 A MAIN CIRCUI T BREAKER 240V 30 A AC INPU T CIRCUI T BREAKER 120V 20 A CIRCUI T BREAKER 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 1...

Страница 44: ...e L2 receptacle group is 22 5A Figure 24 9PXTFMR5 L2 Load Output Limits 4 5 20R 1 L14 30R CIRCUI T BREAKER 240V 30 A CIRCUI T BREAKER 240V 50A 208V 240V SELEC T OUTPU T 120V 20 A OUTPU T 120V 20 A CIRCUI T BREAKER 240V 20 A CIRCUI T BREAKER 240V 20 A OUTPU T 120 240V 30 A OUTPU T 120 240V 30 A CIRCUI T BREAKER 240V 30 A OUTPU T NORMA L AC SOURCE L1 N L2 L1 L 2 N 1 L14 30R 208V When the input volta...

Страница 45: ...ltage is 240V the total output current maximum is 45 8A for either the L2 receptacle group or the L 2 terminal 9PXTFMR11 L 2 Terminal 9PXTFMR11 L2 Receptacle Group 4 5 20R 1 L14 30R 1 L14 30R Figure 26 9PXTFMR11 L2 L 2 Output Limits 1 L14 30R 3 5 20R 1 L6 30R 9PXPPDM1 L1 Receptacle Group 208V When the input voltage is 208V the total output current maximum for the L1 receptacle group is 22 1A 240V ...

Страница 46: ...Output Limits System Configuration Connections This section provides illustrations of 9PX PPDM and 9PX Transformer system configuration connections NOTE The installation diagrams in this section depict rack configurations Although the orientation is different the system connections are the same for tower configurations NOTE Refer to the UPS user s guide for additional installation and system confi...

Страница 47: ...ected to UPS Output Connector UPS 9PXTFMR5 Figure 29 9PXTFMR5 with 9PX5000 or 9PX6000 UPS Kits 9PX5KTF5 and 9PX6KTF5 9PX PPDM Connected to AC Source Input Power Input from 9PX PPDM Connected to UPS Output Connector Input from UPS Connected to 9PX PPDM Output Connector UPS 9PXPPDM1 Figure 30 9PXPPDM1 with 9PX5000 or 9PX6000 UPS Kits 9PX5KP1 and 9PX6KP1 ...

Страница 48: ...ted to UPS Output Connector Figure 31 9PXPPDM2 with 9PX5000 or 9PX6000 UPS Kits 9PX5KP2 and 9PX6KP2 MBP Connected to AC Source Input Power From MBP UPS Input Connection to UPS Normal AC Source Connection Input from 9PX Transformer Connected to MBP Output Connector UPS 9PXTFMR5 EBM and MBP MBP Output to UPS Output Communication Connection for Detecting the MBP Figure 32 9PXTFMR5 11k 240V EBM and 11...

Страница 49: ... Connected to AC Source Input Power Load Output If Terminal Block Wired Load Output If Plugged into Receptacles Output from UPS Connected to 9PX Transformer Normal AC Source Input Connector EBM 9PXTFMR11 UPS EBM 9PXTFMR11 UPS Figure 33 9PXTFMR11 and 11k 240V EBM with 9PX11000 UPS Kit 9PX11KTF11 ...

Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44 ...

Страница 51: ...feature is resident on the 9PXPPDM1 and 9PXPPDM2 models NOTE You can assemble a system configuration that provides maintenance bypass by adding a 9PX Maintenance Bypass MBP See Figure 32 on page 42 for an illustration of that configuration Using Maintenance Bypass To transfer your equipment to maintenance bypass AC Line operation and remove the UPS 1 Using the UPS LCD menu Control Go to Bypass pla...

Страница 52: ...able from the UPS Disconnect the 9PX PPDM input and output cords from the UPS see System Configuration Connections on page 40 for connection illustrations 8 Remove the UPS Return to Normal UPS Protection To reinstall the UPS and transfer your equipment from Maintenance Bypass AC Line operation to the UPS 1 If optional Extended Battery Modules EBMs are installed switch the battery circuit breaker o...

Страница 53: ...ut voltage through the front panel refer to the UPS user s guide 6 On the 9PX PPDM front cover unsnap and remove the square center cover 7 Turn the bypass switch on the 9PX PPDM to the UPS normal position see Figure 35 208V 2 4 0 V NORMAL BYPASS Figure 35 Setting the Bypass Switch to UPS Normal 8 Using the UPS LCD menu force the UPS to Normal mode Control Go back Normal The indicator remains on in...

Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48 ...

Страница 55: ...ncondensing Altitude 10 derating over 1000m The altitude shall not exceed 3000m Dimensions WxDxH 440 645 130 mm 17 3 25 4 5 1 440 645 130 mm 17 3 25 4 5 1 440 685 130 mm 17 3 27 0 5 1 440 700 130 mm 17 3 28 0 5 1 Weight 43 5 kg 96 lb 44 5 kg 98 lb 44 5 kg 98 lb 85 kg 187 lb Table 12 Input Specifications Model Number Input Sine Wave Waveform Input Voltage Input Current Input Voltage Range UPS on By...

Страница 56: ... Output Voltage Efficiency Voltage Adjustable Frequency Range Output Protection 9PXTFMR5 5000 VA 5000W 120V 2 isolated 92 Linear Load 4 60 Hz 3 Hz 1 UL 489 type 30A double pole CB 4 UL 489 type 20A CB 9PXPPDM1 6000 VA 6000W 120V 2 isolated 240V 1 isolated 95 Linear Load 4 46 65 Hz 1 UL 489 type 30A double pole CB 2 UL 489 type 20A CB 9PXPPDM2 6000 VA 6000W 120V 2 isolated 240V 1 isolated 95 Linear...

Страница 57: ...ategories C2 CISPR22 Class A FCC Part 15 Class A Table 15 Power Connections Model Input Connection Output Outlets 9PXTFMR5 1 L6 30P power cord 0 9m 2 3 ft 18 5 20R 9PXPPDM1 1 L6 30P power cord 0 9m 2 3 ft 1 L14 30R 1 L6 30R 6 5 20 R 9PXPPDM2 Hardwired Terminal Block 65A 250V 3 Hardwired Terminal Block 65A 250V 4 9PXTFMR11 Hardwired Terminal Block 65A 250V 3 Hardwired Terminal Block 65A 250V 4 and ...

Страница 58: ... 120V 20 A MAIN CIRCUI T BREAKER 240V 30 A AC INPU T CIRCUI T BREAKER 120V 20 A CIRCUI T BREAKER 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A CIRCUI T BREAKER 120V 20 A Output to UPS 1 Main Circuit Breaker One 240V 30A 2 Output Circuit Breakers Two 120V 20A 2 Output Circuit Breakers Two 120V 20A 18 5 20R Output Receptacles Fi...

Страница 59: ...PDM2 CIRCUIT BREAKER 240V 30 A OUTPUT NORMAL AC SOURCE CIRCUIT BREAKER 240V 50A 208V 240V SELECT OUTPUT 120V 20 A OUTPUT 120V 20 A CIRCUIT BREAKER 240V 20 A CIRCUIT BREAKER 240V 20 A OUTPUT 120 240V 30 A OUTPUT 120 240V 30 A CIRCUIT BREAKER 240V 30 A 2 L14 30R Output Receptacles 8 5 20R Output Receptacles 2 Output Circuit Breakers Two 120V 20A 1 Output Circuit Breaker One 240V 50A Output to UPS Op...

Страница 60: ...R Output Receptacle 6 5 20R Output Receptacles 1 Main Circuit Breaker One 240V 30A 2 Output Circuit Breakers Two 120V 20A AC Source CIRCUI T BREAKER 120V 20 A OUTPU T 120V 20 A OUTPU T 120V 20 A CIRCUI T BREAKER 120V 20 A OUTPU T 120 240V 30 A OUTPU T 240V 30 A MAIN CIRCUI T BREAKER 240V 30 A TO UPS INPU T NORMA L AC SOURCE FROM UPS OUTPU T Figure 39 9PXPPDM1 ...

Страница 61: ...ed behind the UPS front cover S Version number if available S Date of failure or problem S Symptoms of failure or problem S Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging f...

Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56 ...