ELECTRICAL INSTALLATION
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
20
9PXTFMR11 Electrical Installation
This section provides terminal block wiring requirements and electrical
installation procedures for the 9PXTFMR11 model.
Requirements
The 9PXTFMR11 model requires a dedicated branch circuit that meets
the following requirements:
S
80A circuit with short circuit and overcurrent protection
S
208/240 Vac
S
Single phase
S
50/60 Hz
S
Breaker must be wall-mounted and readily accessible to the operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)
Figure 11 shows the 9PXTFMR11 block diagram. The 9PXTFMR11 I/O
terminal block is hardwired. The voltage selection terminal block must
be wired with flexible wiring.
Voltage
Selection
L1
L2
G
N
Transformer
AC Output
120
120
240
Transformer
AC Input
L1
L2
G
(To UPS
Output)
TB (x6)
TB (x4)
240
208
50A CB
L14-30R
L14-30R
5-20R
(x4)
5-20R
(x4)
G
20A CB
20A CB
30A CB
30A CB
Figure 11. 9PXTFMR11 Block Diagram
Содержание PowerPass 9PXTFMR5
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4 ...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6 ...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14 ...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34 ...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44 ...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48 ...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56 ...