260 Parameters
Defines the “at setpoint” limits for torque control of the
drive. When the absolute difference between reference
(
) and actual torque (
) is smaller than
the drive is considered to be “at setpoint”. This is indicated
by bit 8 of
5.0%
0.0…300.0%
Limit for “at setpoint” indication in torque control.
See par.
Defines the trigger level for “above limit” indication in
speed control. This is indicated by bit 10 of parameter
and parameter
. When actual speed exceeds
the limit, bit 10 of
is set.
1500.00 rpm
0.00…30000.00 rpm
“Above limit” indication trigger level for speed control.
See par.
Defines the trigger level for “above limit” indication in
frequency control. This is indicated by bit 10 of parameter
and parameter
. When actual frequency
exceeds the limit, bit 10 of
is
set.
50.00 Hz
0.00…1000.00 Hz
“Above limit” indication trigger level for frequency control.
See par.
Defines the trigger level for “above limit” indication in
torque control. This is indicated by bit 10 of parameter
and parameter
. When actual torque exceeds
the limit, bit 10 of
is set.
300.0%
0.0…1600.0%
“Above limit” indication trigger level for torque control.
See par.
Defines the trigger level for the “kWh pulse” on for 50 ms.
The output of the pulse is bit 9 of
1.000 kWh
0.001…
1000.000 kWh
“kWh pulse” on trigger level.
1 = 1 kWh
No.
Name/Value
Description
Default
FbEq 16
(%)
0%
(%)
Drive at setpoint
bit 8 = 1)