202 Parameters
EFB
Only for the DCU profile. DCU control word bit 15 received
through the embedded fieldbus interface.
11
-
Defines a minimum torque limit for the drive (in percent of
nominal motor torque). See diagram at parameter
The limit is effective when
• the source selected by
is 0, or
•
WARNING!
Do not use minimum torque to stop
reverse rotation of the motor. Usage of minimum
torque limits disables the drive to reach zero speed
and fails to stop the motor.
-300.0%
-1600.0…0.0%
Minimum torque limit 1.
See par.
Defines a maximum torque limit for the drive (in percent of
nominal motor torque). See diagram at parameter
The limit is effective when
• the source selected by
is 0, or
•
300.0%
0.0…1600.0%
Maximum torque 1.
See par.
Defines the source of the minimum torque limit for the
drive (in percent of nominal motor torque) when
• the source selected by parameter
is
1, or
•
Note:
Any positive values received from the selected
source are inverted.
Zero
None.
0
AI1 scaled
1
AI2 scaled
2
PID
(output of the process
PID controller).
15
Minimum torque 2
16
-
Defines the source of the maximum torque limit for the
drive (in percent of nominal motor torque) when
• the source selected by parameter
is
1, or
•
Note:
Any negative values received from the selected
source are inverted.
Zero
None.
0
AI1 scaled
1
AI2 scaled
2
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 202 Tuesday, March 9, 2021 2:25 PM