Parameters 257
Monthly peak power
value (resettable)
Value of the peak power during the present month, that is,
since midnight of the first day of the present month.
You can reset the value by setting it to zero.
0.00 kW
-3000.00 … 3000.00
kW
Peak power value.
10 = 1 kW
Date of the peak power during the present month.
1/1/1980
1/1/1980...6/5/2159
Date.
N/A
Time of the peak power during the present month.
00:00:00
Time.
N/A
Monthly total energy
(resettable)
Total energy consumption from the beginning of the
present month.
You can reset the value by setting it to zero.
0.00 kWh
-1000000.00 …
1000000.00 kWh
Total energy.
0.01 = 1 kWh
Total energy consumption during the previous month, that
is, between midnight of the first day or the previous month
and midnight of the first day of the present month.
0.00 kWh
-1000000.00 …
1000000.00 kWh
0.01 = 1 kWh
Value of the peak power over the drive lifetime.
0.00 kW
-3000.00 … 3000.00
kW
Peak power value.
10 = 1 kW
Date of the peak power over the drive lifetime.
1/1/1980
Date.
N/A
Time of the peak power over the drive lifetime.
00:00:00
Time.
N/A
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
to parameter
).
Also defines the 16-bit scaling of speed-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
1500.00 rpm
0.10…30000.00 rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 257 Tuesday, March 9, 2021 2:25 PM