22 Start-up, ID run and use
- The number of motors can change.
- The nominal motor current is less than 20% of the nominal drive current.
Scalar mode is not recommended for permanent magnet motors.
5. Set the nominal motor values:
•
Nominal power
•
Nominal current
•
Nominal voltage
•
Nominal frequency
•
Nominal speed
•
Nominal torque (optional)
•
Nominal cosphi (optional)
6. Examine the direction of the motor.
If it is necessary, set the motor direction with the
Phase order
setting or with the
phase order of the motor cable.
7. In the
Motor control
view
,
set the start and stop mode.
8. Set the acceleration time and the deceleration time.
Note:
The speed acceleration and deceleration ramp times are based on the
value in parameter
/
9. Set the maximum and minimum speed or frequency. For more information, see
parameters
/
on page
10. In the
Control macros
view, select the applicable macro.
11. Tune the drive parameters to the application. You can use the Assistant control
panel (ACS-AP-x), or the Drive Composer PC tool with the drive.
Do the identification (ID) run
Background information
The drive automatically estimates motor characteristics using Standstill ID run when
the drive is started for the first time, and after any motor parameter (group
) is changed. This is valid when:
• parameter
selection is
and
• parameter
selection is
.