Control macros 31
Terminal sizes: 0.5 mm² … 1 mm²
Notes:
1)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
2)
Select voltage or current for inputs AI1 and AI2 and output AO with parameters
and
Input signals
• Speed analog reference, Hand (AI1)
• Speed analog reference, Auto (AI2)
• Start/stop selection, Hand (DI1)
• Hand(1)/Auto(0) selection (DI2)
• Start/stop selection, Auto (DI3)
• Fault reset (DI4)
Output signals
• Digital output: Running
• Relay output: Fault(-1)
• Analog output AO: Output frequency