208 Parameters
Defines the fault that can be automatically reset using
parameter
, bit 10.
(page
).
Note:
The fault codes are in hexadecimal. The selected
code must be converted to decimal for this parameter.
0
0000h…FFFFh
Fault code.
10 = 1
Defines the maximum number of automatic resets that the
drive is allowed to attempt within the time defined by
parameter
.
If the fault persists, subsequent reset attempts will be
made at intervals defined by
.
The faults to be automatically reset are defined by
0
0…5
Number of automatic resets.
10 = 1
Defines a time window for automatic fault resets. The
maximum number of attempts made during any period of
this length is defined by
.
Note
: If the fault condition remains and cannot be reset,
each reset attempt will generate an event and start a new
time window. In practice, if the specified number of resets
(
) at specified intervals (
) take longer than the
value of
, the drive will continue to attempt resetting
the fault until the cause is eventually removed.
30.0 s
1.0…600.0 s
Time for automatic resets.
10 = 1 s
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
0.0 s
0.0…120.0 s
Autoreset delay.
10 = 1 s
Selects how the drive reacts when a motor phase loss is
detected. See section
on page
No action
No action taken.
0
Fault
The drive trips on fault
1
Selects how the drive reacts when a supply phase loss is
detected.
No action
No action taken.
0
Fault
The drive trips on fault
1
No.
Name/Value
Description
Default
FbEq 16