Parameters 259
Defines a filter time for signal
.
100 ms
2…20000 ms
Output power signal filter time.
1 = 1 ms
Defines the “at setpoint” limits for speed control of the
drive.
When the difference between reference (
) and the speed (
) is smaller than
, the
drive is considered to be “at setpoint”. This is indicated by
bit 8 of
.
50.00 rpm
0.00…30000.00 rpm
Limit for “at setpoint” indication in speed control.
See par.
Defines the “at setpoint” limits for frequency control of the
drive. When the absolute difference between reference
(
Frequency ref ramp input
) and actual frequency
(
01.06
Output frequency
) is smaller than
46.22
At
frequency hysteresis
, the drive is considered to be “at
setpoint”. This is indicated by bit 8 of
Main status
word
.
2.00 Hz
0.00…1000.00 Hz
Limit for “at setpoint” indication in frequency control.
See par.
No.
Name/Value
Description
Default
FbEq 16
(rpm)
0 rpm
(rpm)
(rpm)
(rpm)
Drive at setpoint
bit 8 = 1)
(Hz)
0 Hz
46.22
(Hz)
46.22
(Hz)
Drive at setpoint
bit 8 = 1)
ACS180 FW.book Page 259 Tuesday, March 9, 2021 2:25 PM