244 Parameters
Defines a boost time for the sleep boost step. See
parameter
.
0.0 s
0.0…3600.0 s
Sleep boost time.
1 = 1 s
When the drive is entering sleep mode, the process
setpoint is increased by this value for the time defined by
parameter
.
If active, sleep boost is aborted when the drive wakes up.
0.0 PID
customer
units
0.0…200000.0 PID
customer units
Sleep boost step.
1 = 1 PID
customer
unit
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter,
and remains there for the duration of the wake-up delay
(
), the drive wakes up.
See also parameter
.
0.00 PID
customer
units
-200000.00...200000.0
PID customer units
Wake-up level (as deviation between process setpoint
and feedback).
1 = 1 PID
customer
unit
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
.
The delay timer starts when the deviation exceeds the
wake-up level (
), and resets
if the deviation falls below the wake-up level.
0.50 s
0.00…60.00 s
Wake-up delay.
1 = 1 s
Activates (or selects a source that activates) tracking
mode. In tracking mode, the value selected by parameter
is substituted for the PID
controller output. See also section
1 = Tracking mode enabled
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
21
Supervision 2
Bit 1 of
22
Supervision 3
Bit 2 of
23
Supervision 4
Bit 3 of
Supervision 5
Bit 4 of
Supervision 6
Bit 5 of
-
Selects the value source for tracking mode. See
parameter
Not selected
None.
0
No.
Name/Value
Description
Default
FbEq 16