94 Program features
Overspeed protection (parameter
The user can set overspeed (and overfrequency) limits by specifying a margin that is
added to the currently-used maximum and minimum speed (or frequency) limits.
Local control loss detection (parameter
)
The parameter selects how the drive reacts to a control panel or PC tool
communication break.
The parameters select how the drive reacts when an analog input signal moves out of
the minimum and/or maximum limits specified for the input.
Ramp stop supervision (parameters
,
and
The control program has a supervision function for both the normal and emergency
stop ramps. The user can either define a maximum time for stopping, or a maximum
deviation from the expected deceleration rate. If the drive fails to stop in the expected
manner, a fault is generated and the drive coasts to a stop.
Custom motor current fault limit (parameter
)
The control program sets a motor current limit based on drive hardware. In most
cases, the default value is appropriate. However, a lower limit can be manually set by
the user, for example, to protect a permanent magnet motor from demagnetization.