Parameters 135
Defines the filter time constant for analog input AI2. See
parameter
.
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This
cannot be changed by any parameter.
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
4.000 mA or
0.000 V
0.000…22.000 mA
or 0.000…11.000 V
Minimum value of AI2.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
20.000 mA
or 10.000 V
0.000…22.000 mA
or 0.000…11.000 V
Maximum value of AI2.
1000 = 1 mA
or V
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
12.27
AI2
min
. (Changing the polarity settings of
12.29
and
12.101
can effectively invert the analog input.)
0.000
-32768.000…
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
. See the drawing at parameter of
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
Value of analog input AI1 in percent of AI1 scaling (
-
0.00… 100.00
AI1 value
100 = 1%
Value of analog input AI2 in percent of AI1 scaling (
-
0.00… 100.00
AI2 value
100 = 1%
No.
Name/Value
Description
Default
FbEq 16
12.101
12.28
12.27
12.29
AI
in
(
12.21
)
AI
scaled
(
12.22
)
ACS180 FW.book Page 135 Tuesday, March 9, 2021 2:25 PM