Control macros 35
Notes
:
Set the communication mode jumper to Modbus Mode. EIA-485 Modbus RTU can't
be used together with external panel.
1)
Select voltage or current for inputs AI1 and AI2 and output AO with parameters
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
Input signals
• Constant speed selection 1 (AI1)
• Speed reference, Hand (AI2)
• Start/stop selection, Hand (DI1)
• Forward/Reverse selection, Hand (DI2)
• Hand(1)/Modbus(0) selection (DI3)
• Fault reset (DI4)
Output signals
• Digital output: Running
• Relay output: Fault(-1)
• Analog output AO: Output frequency