Parameters 271
LO-HI
The first register contains the low order word, the second
contains the high order word.
1
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to the register
address corresponding to Modbus register 1 (400001).
The master defines the type of the data (input or output).
The value is transmitted in a Modbus frame consisting of
two 16-bit words. If the value is 16-bit, it is transmitted in
the LSW (least significant word). If the value is 32-bit, the
subsequent parameter is also reserved for it and must be
set to
None
.
None
No mapping, register is always zero.
0
CW 16bit
CiA402
and
Transparent 16 profiles: 16-bit
: lower 16 bits of the DCU
control word
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
SW 16bit
profile: 16-bit ABB drives status word;
: lower 16 bits of the DCU status word
4
Act1 16bit
Actual value ACT1 (16 bits)
5
Act2 16bit
Actual value ACT2 (16 bits)
6
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
SW 32bit
Status Word (32 bits)
14
Act1 32bit
Actual value ACT1 (32 bits)
15
Act2 32bit
Actual value ACT2 (32 bits)
16
CW2 16bit
profile: not used;
: upper 16 bits of
the DCU control word
21
SW2 16bit
profile: not used / always zero;
upper 16 bits of the DCU status word.
24
RO/DIO control word
Parameter
31
AO1 data storage
Parameter
.
32
Feedback data
storage
Parameter
.
40
Setpoint data storage
Parameter
41
).
-
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400002.
For the selections, see parameter
.
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400003.
For the selections, see parameter
.
No.
Name/Value
Description
Default
FbEq 16