140 Parameters
Defines the maximum output value for analog output AO1.
See also drawing at parameter
.
20.000 mA
0.000…22.000 mA
0.000…11.000 V
Maximum AO1 output value.
1000 = 1 mA
Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In parameter
, select
.
Then set this parameter as the target of the incoming
value data. With the embedded fieldbus interface, simply
set the target selection parameter of that particular data
(
…
0.00
-327.68 … 327.67
Storage parameter for AO1.
100 = 1
15
Selection of local and external control location sources
and operating modes.
See section
in chapter
.
Displays the operating mode currently used.
See parameters
…
.
This parameter is read-only.
Zero
None.
1
Speed
Speed control (in vector motor control mode).
2
Torque
Torque control (in vector motor control mode).
3
Min
The torque selector is comparing the output of the speed
controller (
25.01 Torque reference speed control
) and
torque reference (
) and the
smaller of the two is used (in vector motor control mode).
4
Max
The torque selector is comparing the output of the speed
controller (
25.01 Torque reference speed control
) and
torque reference (
) and the
greater of the two is used (in vector motor control mode).
5
Add
The speed controller output is added to the torque
reference (in vector motor control mode).
6
Reserved
7…9
Scalar (Hz)
Frequency control in scalar motor control mode.
10
Forced magn.
Motor is in magnetizing mode.
20
Selects the source for external control location
EXT1/EXT2 selection.
0 = EXT1
1 = EXT2
EXT1
EXT1 (permanently selected).
0
EXT2
EXT2 (permanently selected).
1
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
Supervision 1
Bit 0 of
25
No.
Name/Value
Description
Default
FbEq 16