136 Parameters
13
Configuration of standard analog outputs.
Selects the analog outputs that will be forced to values
defined by parameters.
The true source signals of the analog outputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog output, and its
value is applied whenever the corresponding bit in this
parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
and
0000h
0000h…FFFFh
Forced values selector for analog output AO1.
1 = 1
Displays the value of AO1 in mA or V.
This parameter is read-only.
-
0.000…22.000 mA
0.000…11.000 V
Value of AO1.
1 = 1 mA
Selects a signal to be connected to analog output AO1.
Zero
None. 0
Motor speed used
1
Output frequency
3
Motor current
4
Motor current % of
motor nom
5
Motor torque
6
DC voltage
7
Output power
8
Speed ref ramp in
10
Speed ref ramp out
11
Speed ref used
12
Freq ref used
14
Process PID out
40.01 Process PID output actual
16
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
20
Abs motor speed used
26
Abs motor speed %
27
Abs output frequency
28
Abs motor torque
30
Abs output power
31
Abs motor shaft power
32
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force AO1 to value of parameter
AO1 forced value
.
1…15
Reserved.