170 Parameters
Defines the change rate of the motor potentiometer. This
parameter specifies the time required for the motor
potentiometer to change from minimum (parameter
)
to maximum (parameter
). The same change rate
applies in both directions.
40.0 s
0.0…3600.0 s
Motor potentiometer change time.
1 = 1 s
Defines the minimum value of the motor potentiometer.
Note:
If vector control mode is used, the value of this
parameter must be changed.
-50.00
-32768.00… 32767.00 Motor potentiometer minimum.
1 = 1
Defines the maximum value of the motor potentiometer.
Note:
If vector control mode is used, the value of this
parameter must be changed.
50.00
-32768.00… 32767.00 Motor potentiometer maximum.
1 = 1
Shows the output of the motor potentiometer function.
(The motor potentiometer is configured using parameters
.)
This parameter is read-only.
-
-32768.00… 32767.00 Value of motor potentiometer.
1 = 1
Displays the value of the speed reference (Ext1 or Ext2)
that has been selected by
. See
diagram at
or the control chain
diagram on page
This parameter is read-only.
0.00 rpm
-30000.00… 30000.00
rpm
Speed reference after additive 2.
See par.
Displays the value of speed reference before application
of critical speeds. See the control chain diagram on page
unless overridden by
• any constant speed
• a jogging reference
• network control reference
• control panel reference
• safe speed reference.
This parameter is read-only.
0.00 rpm
-30000.00… 30000.00
rpm
Speed reference before application of critical speeds.
See par.
23
Speed reference ramp settings (programming of the
acceleration and deceleration rates for the drive).
See the control chain diagram on page
Displays the used speed reference (in rpm) before it
enters the ramping and shaping functions. See the control
chain diagram on page
This parameter is read-only.
-
-30000.00… 30000.00
rpm
Speed reference before ramping and shaping.
See par.
No.
Name/Value
Description
Default
FbEq 16