Parameters 147
Selects source 2 for parameter
For the available selections, see parameter
Selects source 3 for parameter
For the available selections, see parameter
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by
parameter
Coast
Stop by switching off the output semiconductors of the
drive. The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure
it is safe to stop the drive by coasting.
0
Ramp
Stop along the active deceleration ramp. See parameter
group
1
Torque limit
Stop according to torque limits (parameters
).
2
Selects the source of the external run enable signal. If the
run enable signal is switched off, the drive will not start. If
already running, the drive will stop according to the setting
of parameter
.
1 = Run enable signal on.
See also parameter
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
24
Supervision 2
Bit 1 of
25
Supervision 3
Bit 2 of
26
Supervision 4
Bit 3 of
27
Supervision 5
Bit 4 of
28
Supervision 6
Bit 5 of
29
EFB MCW bit 3
Control word bit 3 received through the embedded
fieldbus interface.
32
).
-
Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is
running will not stop the drive.)
See also parameter
.
Off
0.
0
No.
Name/Value
Description
Default
FbEq 16