266 Parameters
Displays the status of the EFB communication.
This parameter is read-only.
Note that the name is only visible when the error is
present (bit value is 1).
-
0000h…FFFFh
EFB communication status.
1 = 1
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
-
0…4294967295
Number of received packets addressed to the drive.
1 = 1
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
-
0…4294967295
Number of transmitted packets.
1 = 1
Displays a count of valid packets addressed to any device
on the bus. During normal operation, this number
increases constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
-
0…4294967295
Number of all received packets.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
and
6
Baud rate error
1 = Error detected: check parameters
and
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
11
CW/Ref loss
1 = No control word or references received within timeout (
12
Not active
Reserved
13
Protocol 1
Reserved
14
Protocol 2
Reserved
15
Internal error
1 = Internal errors detected