232 Parameters
Warning/Fault
The drive generates an
if the
signal has been continuously over the overload curve for
half of the time defined by parameter
if the signal
has been continuously over the overload curve for a time
defined by parameter
3
Selects an action taken if the signal (
) stays under
the underload curve for a defined time.
Disabled
No warnings or fault generated.
0
Warning
if
the signal has been continuously under the underload
curve for a time defined by parameter
.
1
Fault
if the signal
has been continuously under the underload curve for a
time defined by parameter
.
2
Warning/Fault
if
the signal has been continuously under the underload
curve for half of the time defined by parameter
.
if the signal
has been continuously under the underload curve for a
time defined by parameter
.
3
Defines the first of the five speed points on the X-axis of
the user load curve.
The values of the parameters must satisfy: -30000.0 rpm
<
30000.0 rpm.
Speed points are used if parameter
is set to
is set
and the reference unit is rpm.
The five points must be in order from lowest to highest.
The points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
150.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the second speed point.
See parameter
750.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the third speed point.
See parameter
1290.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the fourth speed point.
See parameter
1500.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 232 Tuesday, March 9, 2021 2:25 PM