Parameters 233
Defines the fifth speed point.
See parameter
.
1800.0 rpm
-30000.0…30000.0
rpm
Speed. 1
=
1 rpm
Defines the first of the five frequency points on the X-axis
of the user load curve.
The values of the parameters must satisfy: -500.0 Hz <
37.16 ULC frequency table point 1
37.18 ULC frequency table point 3
< 500.0 Hz.
Frequency points are used if parameter
is set to
and the reference unit is Hz.
The five points must be in order from lowest to highest.
The points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
5.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the second frequency point.
See parameter
37.16 ULC frequency table point 1
25.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the third frequency point.
See parameter
37.16 ULC frequency table point 1
43.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the fourth frequency point.
See parameter
37.16 ULC frequency table point 1
50.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the fifth frequency point.
See parameter
37.16 ULC frequency table point 1
60.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the first of the five points on the Y-axis that
together with the corresponding point on the X-axis (
or
…
) define the underload (lower) curve.
The following conditions must be fulfilled:
•
•
•
•
•
10.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the second underload point.
See parameter
15.0%
-1600.0…1600.0%
Underload point.
1 = 1%
No.
Name/Value
Description
Default
FbEq 16