Parameters 215
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note:
This parameter does not affect the status indicated
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
The drive trips on fault
.
2
Fault if running
The drive trips on fault
if running. 3
Selects the signal to be monitored by signal supervision
function 1.
Zero
None.
0
Speed
.
1
Frequency
3
Current
4
Torque
DC voltage
.
7
Output power
.
8
AI1
.
9
AI2
10
Speed ref ramp in
.
18
Speed ref ramp out
19
Speed ref used
20
Torque ref used
.
21
Freq ref used
22
Inverter temperature
23
Process PID output
24
Process PID feedback
25
Process PID setpoint
.
26
Process PID deviation
.
27
).
-
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 1.
0.00
-21474830.00…
21474830.00
Low limit.
-
Defines the upper limit for signal supervision 1.
0.00
-21474830.00…
21474830.00
Upper limit.
-
No.
Name/Value
Description
Default
FbEq 16