Parameters 183
Control panel (ref
copied)
Panel reference (
) for
the previous control location is used as the reference
when the control location changes if the references for the
two locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal
is used as the new reference.
19
Integrated panel (ref
saved)
See above Control panel (ref saved)
20
Integrated panel (ref
copied)
See above Control panel (ref copied).
21
Frequency input 2
(when DI3 or DI4 is used as a
frequency input).
22
).
-
Selects torque reference source 2.
For the selections, and a diagram of reference source
selection, see parameter
Selects a mathematical function between the reference
sources selected by parameters
and
Ref1
Signal selected by
is used as
torque reference 1 as such (no function applied).
0
Add (ref1 + ref2)
The sum of the reference sources is used as torque
reference 1.
1
Sub (ref1 - ref2)
The subtraction ([
] - [
]) of the reference sources is used as
torque reference 1.
2
Mul (ref1 × ref2)
The multiplication of the reference sources is used as
torque reference 1.
3
Min (ref1, ref2)
The smaller of the reference sources is used as torque
reference 1.
4
Max (ref1, ref2)
The greater of the reference sources is used as torque
reference 1.
5
Configures the selection between torque references 1 and
2. See diagram at
0 = Torque reference 1
1 = Torque reference 2
Torque reference 1
0.
0
Torque reference 2
1.
1
Follow Ext1/Ext2
selection
Torque reference 1 is used when external control location
EXT1 is active. Torque reference 2 is used when external
control location EXT2 is active.
See also parameter
.
2
DI1
Digital input DI1 (
, bit 0).
3
No.
Name/Value
Description
Default
FbEq 16
Ext1 -> Ext2
Ext1 reference
Ext2 reference
Active reference
t
Inactive reference
Reference