354 Fieldbus control through the embedded fieldbus interface (EFB)
Modbus parameter settings for embedded fieldbus interface
Parameter
Setting for
fieldbus control
Function/Information
COMMUNICATION INITIALIZATION
Initializes embedded fieldbus communication.
EMBEDDED MODBUS CONFIGURATION
1 (default)
Node address. There must be no two nodes
with the same node address online.
(default) Defines the communication speed of the link.
Use the same setting as in the master station.
(default) Selects the parity and stop bit setting. Use the
same setting as in the master station.
(default)
Defines the action taken when a
communication loss is detected.
(default)
Enables/disables communication loss
monitoring and defines the means for
resetting the counter of the communication
loss delay.
3.0 s (default)
Defines the timeout limit for the
communication monitoring.
0 ms (default)
Defines a response delay for the drive.
(default)
Selects the control profile used by the drive.
See section
Basics of the embedded fieldbus
(page
).
(default
for
,
,
),
,
Defines the types of fieldbus references 1 and
2. The scaling for each reference type is
defined by parameters
setting, the type is
selected automatically according to the
currently active drive control mode.
(default
for
),
,
,
Defines the types of actual values 1 and 2.
The scaling for each actual value type is
defined by parameters
setting, the type is
selected automatically according to the
currently active drive control mode.
EFB act1
transparent
source
EFB act2
transparent
source
Defines the source of actual values 1 and 2
when the
.