Parameters 207
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
24
Supervision 2
Bit 1 of
25
Supervision 3
Bit 2 of
26
Supervision 4
Bit 3 of
27
Supervision 5
Bit 4 of
28
Supervision 6
Bit 5 of
29
EFB MCW bit 7
Control word bit 7 received through the embedded
fieldbus interface.
32
).
-
Selects faults that are automatically reset. The parameter
is a 16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The number and interval of reset attempts are defined by
parameters
…
.
WARNING!
Before you activate the function, make
sure that no dangerous situations can occur. The
function resets the drive automatically and
continues operation after a fault.
Notes:
• The autoreset function is only available in external
Local and external control locations
(page
).
• Faults related to the Safe torque off (STO) function
cannot be automatically reset.
The bits of this binary number correspond to the following
faults:
0000h
0000h…FFFFh
Automatic reset configuration word.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI supervision fault
4…9
Reserved
10
Selectable fault (see parameter
)
11
External fault 1 (from source selected by parameter
12
External fault 2 (from source selected by parameter
13
External fault 3 (from source selected by parameter
14
External fault 4 (from source selected by parameter
15
External fault 5 (from source selected by parameter