Parameters 119
Drive status word 1.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 1.
1 = 1
Drive status word 2.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 2.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Enabled
1 = Both run enable (see par.
) and start enable (
) signals
are present.
Note:
This bit is not affected by the presence of a fault.
1
Inhibited
1 = Start inhibited. To start the drive, the inhibiting signal (see par.
) must be removed and the start signal cycled.
2
DC charged
1 = DC circuit has been charged
3
Ready to start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control
1 = Drive is in local control
10
Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12
Reserved
13
Start request
1 = Start requested. 0 = When Enable to rotate signal (see par.
) is 0 (rotating of the motor is disabled).
14
Running
1 = Drive is running
15
Reserved
Bit
Name
Description
0
Identification run done 1 = Motor identification (ID) run has been performed
1
Magnetized
1 = The motor has been magnetized
2
Torque control
1 = Torque control mode active
3
Speed control
1 = Speed control mode active
4
Reserved
5
Safe reference active 1 = A “safe” reference is applied by functions such as
parameters
6
Last speed active
1 = A “last speed” reference is applied by functions such as
parameters
7
Reserved
8
Emergency stop failed 1 = Emergency stop failed (see parameters
and
)
9
Jogging active
1 = Jogging enable signal is on
10
Above limit
Actual speed, frequency or torque equals or exceeds the limit
(defined by parameters 46.31...45.33). Valid for both directions
of rotation.
11…12 Reserved
13
Start delay active
) active.
14…15 Reserved