
Parameters 213
Emergency ramp
supervision delay
If parameter
is set to
0%, this parameter defines the maximum time an
emergency stop (mode Off1 or Off3) is allowed to take. If
the motor has not stopped when the time elapses, the
drive trips on
, sets bit 8 of
, and coasts to a stop.
is set to a value other than 0%, this parameter
defines a delay between the receipt of the emergency
stop command and the activation of the supervision. It is
recommended to specify a short delay to allow the speed
change rate to stabilize.
0 s
0…100 s
Maximum ramp-down time, or supervision activation
delay.
1 = 1 s
Selects the warnings to be suppressed. This parameter is
a 16-bit word with each bit corresponding to a warning.
Whenever a bit is set to 1, the corresponding warning is
not logged to event log.
0000h
0000h…FFFFh
Word for disabling warnings.
1 = 1
Selects the stop mode when a non-critical fault occurs.
Coast
Coast
The drive coasts to stop.
0
Emergency ramp
The drive follows the ramp specified for an emergency
stop by parameter
1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Reserved
1
DC link undervoltage
1 = Warning
is suppressed.
2…4
Reserved
5
Emergency stop off2
1 = Warning
is suppressed.
4
Emergency stop off1, off3
1 = Warning
suppressed.
7…15
Reserved
Reserved
ACS180 FW.book Page 213 Tuesday, March 9, 2021 2:25 PM