Procedures in this manual should only be carried out by Trained Service Personnel.
The ZP3 panel is powered from a 230 volt AC primary supply and from a 24 volt DC battery backup
supply.
Primary Supply
Connection to the 230 volt AC primary supply (+10%: -15%), must comply with National wiring
regulations. The wiring shall be permanently connected to the building wiring through a 10 amp 3 core
cable, and a double pole 10 amp isolation switch.
Care must be taken to wire the primary supply to the correct terminals:
Live
= Brown
Neutral = Blue
Earth = Green/Yellow
The earth wire must NOT be omitted.
The incoming mains fuse only breaks the live connection. Be aware that even when the fuse is
withdrawn, there remains dangerous potential on the incoming terminals. It should also be noted that
dangerous potentials can exist at other locations on the PC board even with mains and battery
disconnected.
Back-up Battery Supply
The back-up batteries, although at only 24 volts DC, carry enough charge to be dangerous.
Care must be taken when connecting batteries, or when working in the vicinity of the battery terminals,
to not accidentally cause a short circuit. In particular metallic tools or metallic watch straps, is causing
an accidental short circuit, can cause burns to the user.
SAFETY
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......