ZP3 Fire Control Panel
Maintenance
ZP3 Fire Control Panel Manual
Page 1 - 6
UD1160.M Iss 6 (25/02/2005)
I
M
1.2.3 Annual Service
The following is the schedule for the annual service that must be carried out on the system.
Annual Checks
•
Quarterly service
Repeat the quarterly service checks.
•
Input-Output configuration test
Using a fairly large representative sample, verify by testing that the input-output
mapping operates as programmed. Activate an input, such as a sensor, callpoint, or
interface unit, and verify that the correct outputs operate. Also check that the outputs
function correctly, for example, that they pulse, or operate continuously, that any
delays operate correctly, etc.
•
Building changes check
Visually check that the internal structural layout of the building, including inter-office
partitioning, has not changed from the system specification to such an extent that it
may affect the efficient operation of the fire alarm system.
•
Completion of Service
Restore the system to normal condition, re-enable any disabled devices, re-connect
any disconnected devices, re-connect all external systems that were disconnected for
the testing, and ensure that the system is left in 100% working condition. Advise all
staff and the remote manned centre that testing is complete, and that any alarm now
received must be treated as real.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......