ZP3 Fire Control Panel
System Configuration
ZP3 Fire Control Panel Manual
Page 7 - 8
UD1160.7 Iss 6 (25/02/2005)
I
7
The ZP3 panel incorporates one control-bus, with 1024 addresses, which can be either
inputs or outputs. Refer to the address list for details. These addresses are in 2 groups:
1.
SystemBus
(Group 09)
Addresses 000 - 255
Controls panel functions, including
zones, common leds, and control
keys. Can be used for external
mimic functions. These outputs
are pre-programmed.
2.
UserBus
(Group 10)
Addresses 000 - 767
Freely programmable.
The group-09 range of addresses are pre-programmed to carry out certain functions, for
example, illuminate zone LED's. Where connected outputs are set to addresses in the
group-09 range, then these outputs will automatically mimic the behaviour of the pre-
programmed functions. For example, an output board set to the same address as the zone
LED's, will automatically mimic these LED's, without any panel programming being required.
The group-10 range of addresses is freely programmable. Any outputs connected to the
system, and with their addresses set to any of the group-10 range, would have to be
programmed using the I/O-Mapping function, before they would operate.
Auxiliary Board Addresses
The ZP3 auxiliary boards can be set to assume any address in the SystemBus (group 9) or
UserBus (group 10) address range. Auxiliary boards have 8, 16, or 24 points, which are
addressed sequentially from a base address. The base address is determined by the DIP
switch settings on each board. Refer to the System Address List.
DIP switch settings between 0 and 31 set the addresses within the SystemBus (09) range.
DIP switch settings between 32 and 127 set the addresses within the UserBus (10) range.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......