ZP3 Fire Control Panel
Power Supply
ZP3 Fire Control Panel Manual
UD1160.3 Iss 6 (25/02/2005)
Page 3 - 13
I
3
3.8 External
Power
for
Accessory
Boards
Where the load required for optional accessory boards exceeds the capacity of the ZP3
power supply, it is possible to power these boards from a separate external 24 Volt dc power
supply. This external supply must meet the following criteria.
1.
Output voltage must be in the range 22 - 28 Volts dc.
2.
Output ripple must be a maximum of 200 Mv (peak-peak).
3.
Must comply with the requirements of European Standard EN54-4.
4.
Output capacity must be adequate for the required load, even with batteries
disconnected.
5.
Incorporate standby batteries, sized to provide the required operating period.
6.
The output must be suitably fused.
7.
For reporting faults to the ZP3 fire panel, two have voltage-free changeover contacts
must be provided, one signalling a mains failure, the other signalling a battery fault.
Important:
Do not connect the 0-volts (negative supply) of the external power supply
and the 0-volts (negative supply) of the fire panel. The 2 power supply
systems must remain floating from each other.
Powering optional accessory boards (sounders and outputs) from a separate external
power supply.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......