ZP3 Fire Control Panel
System Configuration
ZP3 Fire Control Panel Manual
Page 7 - 6
UD1160.7 Iss 6 (25/02/2005)
I
7
7.3 Cause and effect functions
7.3.1 Input-Output Mapping
Input/output mapping is software defined rules that allow the inter linking of inputs to outputs
creating a "cause and effect" schedule. Up to 2000 input triggers may be configured to link
with up to 896 outputs. This allows that multiple input conditions can be defined for each
output.
The full details of every input/output map link needs to be specified. An address must be
specified for each output and each input. The options to be configured for a mapping link
are:
Output parameters
Output Mode
The output mode defines whether the output is silencing, non-silencing, dynamic, or pulsed.
Silencing outputs turn-off when the SILENCE ALARMS key on the panel is pressed. Non-
silencing outputs turn-off when the panel is reset. If the output mode is set to dynamic then
the output will ignore the silence or reset keys, and follow the input trigger, ie; it will switch off
when the input is deactivated. A pulsed response activates the output for a single short
period (about 5 seconds) after activation.
The mode also indicates if the output is triggered by any one of its inputs (single-knock), or
whether it requires two input triggers (double-knock).
Output Re-activate Mode
Applicable to silencing outputs only. This allows an output which has been silenced (from a
previous alarm) to be re-activated by two options, either from any new fire alarm in the
system, or only by a new alarm from input devices that are already linked to it in the I/O map.
Output Delay
When an output is triggered, it can be given an elapsed time delay until it activates of 0 - 600
seconds.
Normal Output State
Each output can be individually defined to be normally off (de-energised in the non-alarm
condition, energising on alarm) or normally on (energised in the non-alarm condition, de-
energising on alarm). Normally off is the default setting.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......