ZP3 Fire Control Panel
Maintenance
ZP3 Fire Control Panel Manual
Page 1 - 14
UD1160.M Iss 6 (25/02/2005)
I
M
Calibrate detectors
Menu Path:
Maintenance\ calibrate detectors
The panel automatically calibrates every sensor each 24 hours, at midnight.
This function allows the manual re-calibration of sensors to be done. When initiated a
message "Calibrating…" is displayed on the LCD screen while calibration takes place. This
takes about one minute to complete.
Test
Menu Path:
Maintenance\test
This menu permits automatic and manual test modes to be set up to provide simple one-man
testing of a complete system.
Detector test
Sensors can be individually or globally configured to
"self-test" every 24 hours. This test is done at midnight,
and a report is generated if any sensors fail the test.
The self test routine can be manually initiated from within
this menu for an immediate real time test. The display will
indicate the number of detectors tested and passed. A
fault event is generated if failure occurs. If a printer is
fitted, a report will automatically be printed.
Walk test
The walk test procedure is executed on a zonal basis. A
zone is placed in "walk-test" mode, and the
sensors/devices within the zone are manually tested.
The outputs and alarms for the selected zone are
automatically disabled. At the end of the test, the display
shows the number of devices in the zone, the number
triggered and passed, and the number not triggered and
failed. The respective zone LED on the fire panel will be
lit. A printed report is also produced. If an alarm occurs
in a different zone, the panel cancels the test, and
initiates a real alarm.
Flash faulty led
Enabling this function flashes the LED on a point that
reports a fault. This assists with visually finding and
identification of the device that reports a fault.
Panel Comms enable\disable
Menu Path:
Maintenance\Comms Enable/Disable
Enables or disables PP3 comms to panels on the Network temporarily, without altering their
filters etc. When edited on one panel it replicates to all panels that are configured to be
online via setup, so that they all agree on who is expected to be online.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......