1.4.6 Gas Control Unit
The Gas Control Unit in particular makes extensive use of slots 5 and 6 to indicate status.
These analogues are shown in Table 1.4.4 for slot 5, and Table 1.4.5 for slot 6.
Details
Nominal value
Digital counts
Normal idle value
39 - 65
Manual when door locked
68-100
Loss of signal
< 39
General panel fault
103 – 132
Power supply fault
> 163
Relay operated
141 – 163
Table 1.4.4 Gas Control Unit status - slot 5 (address 1)
Details
Nominal value
Digital counts
Fault – low idle
< 39
Auto released
39 – 65
Manual released
68 – 100
System locked-off (released)
103 – 132
Auto non-released
141 –163
System locked-off (non-released)
166 – 195
Manual (non-released)
> 198
Table 1.4.5 Gas Control Unit status - slot 6 (address 1)
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......