ZP3 Fire Control Panel
EN54 Setup Requirements
ZP3 Fire Control Panel Manual
Page E - 2
UD1160.E Iss 6 (25/02/2005)
I
E
14.
Para 12.5.2 and CEA GEI 1-052 Para 5.2.3 - Under menu \setup\system config\AGV\
the AGV should be defined enabled for partial short circuit check.
15.
Para 12.5.2 - Loops must be wired in "class A" return loop configuration.
16.
Para 12.5.2 - Isolators should be placed on the loop, such that no more than 32
detectors/callpoints may be isolated in the event of an open or short circuit on the
loop. (It is recommended that no more than 32 points are included in a zone).
17.
Para 12.6 - The controls keyswitch should be left on
18.
Para 12.10.2 - The panel audible sounder shall be operated at full volume and not
suppressed.
19.
EN54-2 annexure A
The commissioning key should be off.
20.
Heat sensor elements required to conform to EN54 Part 5 Grade 1 must be set up to
sensitivity 2
21.
To meet the requirements of EN54-2 either as a sounder output (type C) or a output to
fire protection equipment (type G) the output must be monitored and hence a
monitored output accessory board should be used as opposed to a relay output
accessory board or line device.
22.
The facility in the Setup/Points/Settings/Smoke alert delay, must not be used when
setting up to meet EN54-2.
23.
The ZP3 panel approved to EN54 was tested using the internal power supply.
Although option is provided to supply power from an external power supply this should
not be used if compliance with EN54 is essential.
24.
The ZP3 panel approved to EN54 was tested using 11 isolators in a ZP address loop.
Although option is provided to software select up to 16 isolators, a maximum of 11
should be used if compliance with EN54 is essential.
25.
The loop wiring must be shielded with the screens being positively earthed.
Setup to conform to EN54: all paragraph numbers refer to EN54 part 4 unless otherwise
notated.
1.
Para 5.3.1 b) - Charge rate jumper JP6 must be linked to meet the requirements of
EN54 if the battery capacity exceeds 17Ah. (See Sec 3.10 in the manual).
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......