ZP3 Fire Control Panel
ZP3 Panel
ZP3 Fire Control Panel Manual
Page 2 - 4
UD1160.2 Iss 6 (25/02/2005)
I
2
2.2 Specification
Indicators
Fire (Common)
LED (dual)
Red
Indicates when any fire alarm is present
Fault (Common)
LED (dual)
Yellow
Indicates when any fault alarm is present
Disabled (Common)
LED (dual)
Yellow
Indicates when any disabled condition is present
Information (Common)
LED (dual)
Yellow
Indicates when any other or alarm or event is present
Alarms Silenced
LED
Yellow
Indicates when sounders have been silenced
Sound Alarms Key Pressed
LED
Red
Indicates when “Sound Alarms” has been pressed
Night Mode (Optional)
LED
Green
Indicates when panel is in “Night” mode
Day Mode (Optional)
LED
Yellow
Indicates when panel is in “Day” mode
More Alarms
LED
Red
On when there are extra alarms than visible on-screen
Sounders Active
LED
Red
Indicates when field sounders are active
Remote Centre Alarm Active
LED
Red
Indicates when a fire signal has been sent to a RMC
Control Output Active
LED
Red
Indicates when a control output is active
System Fault
LED
Yellow
Indicates a major system or CPU fault
Zone Fault
LED
Yellow
Indicates when a zone, or device in a zone is faulty
Power Fault
LED
Yellow
Indicates a fault with mains or battery supply
Sounder Fault
LED
Yellow
Indicates when a sounder circuit has a fault
Remote Centre Alarm Fault
LED
Yellow
Indicates a fault on the connection to a RMC
Control Output Fault
LED
Yellow
Indicates when a control output circuit has a fault
Zone Disabled
LED
Yellow
Indicates when a complete zone is disabled
Point Disabled
LED
Yellow
Indicates when an individual device/s is disabled
Sounders Disabled
LED
Yellow
Indicates when any sounders are disabled
Remote Centre Alarm Disabled LED
Yellow
Indicates when the RMC connection is disabled
Control Output Disabled
LED
Yellow
Indicates when any control output is disabled
Zone Pre-Alarm
LED
Yellow
Indicates a Pre-Alarm from a zone
Point Pre-Alarm
LED
Yellow
Indicates a Pre-Alarm from an individual device
System Test Mode
LED
Yellow
Indicates that a zone is in a test-mode
Power On
LED
Green
Indicates that the system has power
Switched Outputs (Standard)
Sounder Circuits
(Common/Programmable)
2
Monitored sounder circuits, programmable as one o/p
Sounder Circuits
(Common/Programmable)
2
Monitored sounder circuits, programmable as one o/p
Fire (Common)
1
Voltage-free relay contacts, common to all fire alarms
Fault (Common)
1
Voltage-free relay contacts, common to fault alarms
Remote Manned Centre (Fire)
1
Monitored voltage output to RMC transmitter for fire
Remote Manned Centre (Fault)
1
Monitored voltage output to RMC transmitter for fault
Switched Outputs and Inputs (Optional)
Relay outputs
Up to 896
A total of 896 (768 freely programmable) inputs
Transistor "open-collector" O/P Up to 896
or outputs can be connected to each ZP3 panel.
Sounder-circuit outputs
Up to 896
These inputs and outputs can be a mixture of any of
Monitored Inputs
Up to 896
the standard device types shown.
Optional Printer
24 Character panel-mounted
Built-in
Plain-paper printer with menu-selectable programme
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......