ZP3 Fire Control Panel
Field Wiring
ZP3 Fire Control Panel Manual
Page 5 - 4
UD1160.5 Iss 6 (25/02/2005)
I
5
5.3 The
Z-Loop
5.3.1 Z-Loop Wiring
The addressable Z-Loop can be wired as a class-A return loop, or as class-B single direction
wiring, with spurs. Loop length can be up to 3000 metres, depending upon the type, quantity
and location of devices attached, see the Z-loop parameters in section 5.3.3.
When wired in class-B single direction format, then the loop terminals must be connected
(+)in to (+)out and (-)in to (-)out.
The loop is monitored for open and short circuit. Unused loops must be terminated (+)in to
(+)out and (-)in to (-)out.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......