ZP3 Fire Control Panel
Field Wiring
ZP3 Fire Control Panel Manual
Page 5 - 12
UD1160.5 Iss 6 (25/02/2005)
I
5
5.5 Auxiliary
Boards
5.5.3 ZP3AB-OP24 Transistor Output Board
This is a programmable output board with 24 separate outputs, designed to drive low-power
functions, such as LED's or control relays. This board is suitable for driving remote mimic
panels. The outputs are open-collector transistor outputs, which switch negative (0 volts)
when activated. The opposite side of the output load (LED, etc) must be connected to a
common positive (+24 volts) from the same power supply source as the board.
Each output is allocated a unique address, and programmed to operate from selected inputs
using the I/O-mapping function built into the panel. The ZP3AB-OP24 board connects to the
ZP3panel control bus. If allocated to the UserBus section, up to 768 addresses are
available. These outputs are freely programmable. If allocated to the SystemBus section, a
further 256 addresses are available, which have pre-programmed functions.
Each board is fitted with a dipswitch, which is set to an address between 000and 255. This
determines the address of each output, as specified in the "Software Configuration" Section.
Each output can drive a maximum circuit load of 50 milli-Amperes. If outputs are used to
switch inductive loads, they should be protected with a flyback diode.
The load is provided from the 24 vdc supply connected to the power input terminals. If
connected to the ZP3 panel auxiliary power supply terminals, then this load will be supplied
from the built-in ZP3 power supply. If connected to an external 24 vdc power supply, then
this will supply the load. If externally supplied, do not common the power supplies.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......