ZP3 Fire Control Panel
Maintenance
ZP3 Fire Control Panel Manual
UD1160.M Iss 6 (25/02/2005)
Page 1 - 15
I
M
1.4 Interpretation of analogue readings
1.4.1 Introduction
The panel reads six analogue values from each device, each time it polls that device.
Each value is a whole number that can range from 0 to 255. These values can be interpreted
in order to provide a comprehensive analysis of each device and the system as a whole.
The six readings are listed below in the order in which they are read and conventionally
displayed.
Reading 1
Reference group
Reading 2
Polling group
Reading 3
Device type
Reading 4
Reference (low)
Reading 5
Device status (device analogue reading)
Reading 6
Device specific
The following sections give the meanings of each analogue reading. Reading 6 is only
meaningful for certain specialized devices. It is usually zero.
1.4.2 Reference group
The reference group reading identifies the device reference group type. This value is used
for several purposes:
•
Decide if a device is 'online' (connected) or 'offline' (disconnected).
•
Determine the health of a device and how well the device or the Line Driver Board is
calibrated.
•
To identify if the device is an intrinsically safe device.
The values are interpreted as follows:
0-39
A value in this range indicates to the panel that there is no device at the
polled address. It is offline.
70-100
Values in this range indicate an intrinsically safe device. The norm for
intrinsically safe devices is 84 which indicates best calibration.
197-226
Values in this range indicate a healthy non-intrinsically safe device. The
norm for devices is 213 which indicates best calibration. If a device falls
outside the range 205-218 then it should be re-calibrated.
All others
Any values falling outside the above ranges indicate a very poorly calibrated
or unhealthy device. The panel will treat devices giving out these readings
as invalid.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......