ZP3 Fire Control Panel
Power Supply
ZP3 Fire Control Panel Manual
Page 3 - 14
UD1160.3 Iss 6 (25/02/2005)
I
3
3.9 Monitoring External Power
When using an external power supply unit, the failure of the mains supply, or the failure of
the batteries, charging system, or fuse, can be reported to the ZP3 fire panel, as shown
below. The power supply unit must incorporate two sets of voltage-free contacts, one which
changes-over on mains failure, the other which changes-over on battery fault (disconnected
battery, low or high voltage, etc), charger failure, or fuse failure. These contacts must be
connected to the ZP3 Main Board terminals as shown. When the contact changes state, the
fault is reported to the ZP3 panel, which indicates the appropriate visual and audible alarm,
as well as signalling to the Remote Manned Centre.
Summary of Contents for ZP3
Page 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Page 2: ......
Page 10: ......
Page 12: ......
Page 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Page 30: ......
Page 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Page 64: ......
Page 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Page 82: ......
Page 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Page 92: ......
Page 106: ......
Page 108: ......
Page 128: ......
Page 130: ......
Page 144: ......
Page 150: ......
Page 158: ......
Page 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Page 160: ......
Page 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Page 190: ......
Page 214: ......
Page 216: ......
Page 220: ......