Z41 Pro / Lite / COM
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
158
813, 842
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] Presence State (HVAC)
Auto, Comfort, Standby,
Economy, Building Protection
814, 843
1 Bit
O
C T R - -
DPT_Occupancy
0/1
[Ix] Presence State (Binary)
Binary Value
1 Bit
O
C T R - -
DPT_Ack
0/1
[Ix] Presence: Slave Output
1 = Motion Detected
815, 844
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Ix] Presence Trigger
Binary Value to Trigger the
Presence Detection
816, 845
1 Bit
I
C - - W -
DPT_Ack
0/1
[Ix] Presence: Slave Input
0 = Nothing; 1 = Detection
from slave device
817, 846
2 Bytes
I
C - - W -
DPT_TimePeriodSec
0-65535
[Ix] Presence: Waiting Time
0-65535 s.
818, 847
2 Bytes
I
C - - W -
DPT_TimePeriodSec
1-65535
[Ix] Presence: Listening Time
1-65535 s.
819, 848
1 Bit
I
C - - W -
DPT_Enable
0/1
[Ix] Presence: Enable
According to parameters
820, 849
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] Presence: Day/Night
According to parameters
821, 850
1 Bit
O
C T R - -
DPT_Occupancy
0/1
[Ix] Presence: Occupancy State
0 = Not Occupied; 1 =
Occupied
822, 851
1 Bit
I
C - - W -
DPT_Ack
0/1
[Ix] External Motion Detection
0 = Nothing; 1 = Motion
detected by an external sensor
823, 828, 833, 852,
857, 862
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] [Cx] Detection State (Scaling)
0-100%
824, 829, 834, 853,
858, 863
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] [Cx] Detection State (HVAC)
Auto, Comfort, Standby,
Economy, Building Protection
825, 830, 835, 854,
859, 864
1 Bit
O
C T R - -
DPT_Switch
0/1
[Ix] [Cx] Detection State (Binary)
Binary Value
826, 831, 836, 855,
860, 865
1 Bit
I
C - - W -
DPT_Enable
0/1
[Ix] [Cx] Enable Channel
According to parameters
827, 832, 837, 856,
861, 866
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] [Cx] Force State
0 = No Detection; 1 =
Detection
867, 871
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Ix] Current Temperature
Temperature Sensor Value
868, 872
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm;1 = Alarm
869, 873
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm;1 = Alarm
870, 874
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm;1 = Alarm
875
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
876, 906
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 1
External Sensor Temperature
877, 907
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 2
External Sensor Temperature
878, 908
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Effective Temperature
Effective Control Temperature
879, 909
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode
1-byte HVAC Mode
880, 910
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Special Mode: Comfort
0 = Nothing; 1 = Trigger