1
MT-600/8000 series
MT-615X / MT-8150X
Installation Instruction
1.0 Installation and Startup Guide
Install Environment
Where
Used
The MT-600/8000 Series is designed for industrial. The temperature range of operating
is from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not
be suitable for using in certain outdoor applications. Please consult the factory for
advised usage in outdoor applications.
NEMA
Rating
The MT-600/8000 Series front bezel is NEMA 4 rated. When installed properly in a
NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means
that fluids will not enter the panel during wash downs.
Electrical
Environment
The MT-600/8000 Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Mechanical
Environment
Avoid installing units in environments where severe mechanical vibration or shocks
are present.
2.0 Installation Instructions
2.1 Mounting Instructions
2.1.1 Location Considerations
Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
output modules, contactors, starters and relays, and any other source of electrical interference are located
away from the back of the unit.
Particular note should be taken to the position of variable speed drives and switching power supplies.
Their input and load cables should be screened to a central star earth point.