Z41 Pro / Lite / COM
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
163
364, 372, 380, 388, 396, 404, 412, 420,
428, 436, 444, 452, 460, 468, 476, 484,
492, 500, 508, 516, 524, 532, 540, 548,
556, 564, 572, 580, 588, 596, 604, 612,
620, 628, 636, 644, 652, 660, 668, 676,
684, 692, 700, 708, 716, 724, 732, 740,
748, 756, 764, 772, 780, 788
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Percentage Control
0-100%
2 Bytes
O
C T R - -
DPT_Value_2_Ucount
0 - 65535
[Px][Bx] 2-Byte Unsigned Int
Control
0...65535
2 Bytes
O
C T R - -
DPT_Value_2_Count
-32768 - 32767
[Px][Bx] 2-Byte Signed Int
Control
-32768...32767
2 Bytes
O
C T R - -
9.xxx
-671088.64 - 670760.96
[Px][Bx] 2-Byte Float Control
-671088.64...670760.96
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[Px][Bx] Enumerated Control
0...255
1 Bit
O
C T R - -
DPT_UpDown
0/1
[Px][Bx] Move Shutter
0 = Up; 1 = Down
1 Bit
O
C T R - -
DPT_Switch
0/1
[Px][Bx] Light On/Off
0 = Off; 1 = On
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Px][Bx] Temperature Control
Absolute Float Value
2 Bytes
I/O
C T R W -
DPT_Value_Tempd
-670760.00 - 670760.00
[Px][Bx] Temperature Offset
Control
Relative Float Value
1 Bit
O
C T R - -
DPT_Step
0/1
[Px][Bx] Temperature Offset
Control
0 = Decrease; 1 =
Increase
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Px][Bx] Mode Control
0 = Cool; 1 = Heat
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[Px][Bx] Mode Control
Heat, Cool, Auto, Fan and
Dry
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Px][Bx] Special Mode Control
Comfort, Standby,
Economy, Building
Protection and Auto
1 Byte
I/O
C T R W U
DPT_Scaling
0% - 100%
[Px][Bx] Green Channel
0-100%
1 Bit
O
C T R - -
DPT_Switch
0/1
[Px][Bx] Daily Timer Control
1-Bit Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Px][Bx] Weekly Timer Control
1-Bit Control
1 Bit
I
C T - W U
DPT_Ack
0/1
[Px][Bx] Alarm Confirmation
0 = No Action; 1 = Confirm
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Px][Bx] Chrono-thermostat:
Temperature Setpoint
Absolute Float Value
1 Bit
O
C T R - -
DPT_Bool
0/1
[Px][Bx] Holiday (1-Bit)
0 = Holiday; 1 = Workday
1 Bit
O
C T R - -
DPT_Bool
0/1
[Px][Bx] Holiday (1-Bit)
0 = Workday; 1 = Holiday
1 Bit
O
C T R - -
DPT_Step
0/1
[Px][Bx] Fan Control (1-Bit)
0 = Decrease; 1 =
Increase
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
Auto, 20%, 40%, 60%,
80%, 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
Auto, 25%, 50%, 75%,
100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
Auto, 33%, 67%, 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
Auto, 50%, 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
Auto, 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][Bx] Fan Control (Scaling)
0%, 25%, 50%, 75%,