I-Device with S7 routing
S7 routing is not possible with the procedure above. S7 routing is only
possible if the I-Device and the higher-level I/O controller are configured
in the same network. The device names must not be identical. By using
identical names and extending the name of the I-Device with "-x", this is
detected internally and used appropriately for S7 routing.
13.7 TIA Portal - Option: Deployment PROFIBUS communication
13.7.1
Fast introduction
The PROFIBUS DP master must be configured in the
Project view
. Here the configuration
happens by the sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
storage media - VSD, VSC’ page 111
The configuration of the PROFIBUS DP master should be done with the following
approach:
n
Activating bus functionality by means of a VSC
n
Hardware configuration - CPU
n
Deployment as DP master
or
deployment as DP slave
n
Transfer of the entire project to the CPU
13.7.2
Activating bus functionality by means of a VSC
To use the MPI(PtP) interface X3 as PROFIBUS interface, the PROFIBUS functionality
must be activated by means of a VSC memory card from VIPA.
1.
Plug the VSC memory card from VIPA.
2.
Execute an overall reset.
Chap. 4.13 ‘Overall reset’ page 105
ð
n
The PROFIBUS functionality is enabled.
n
With activating the bus functionality "PROFIBUS DP master", the bus func-
tionality "PROFIBUS DP slave" is also enabled.
13.7.3
Hardware configuration - CPU
Perform a hardware configuration for the CPU.
Chap. 13.3 ‘TIA Portal - Hardware con-
13.7.4
Deployment as PROFIBUS DP master
The hardware configuration described before was performed.
Overview
Steps of configuration
Proceeding
Precondition
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Option: Deployment PROFIBUS communication > Deployment as PROFIBUS DP master
HB300 | CPU | 013-CCF0R00 | en | 19-30